New controller for HE-230 electric heater now available, power supply 230V AC.

ACU DIN controller

900.00 net

ACU controller DIN is a fully functional controller designed for automation systems controlling the operation of supply and exhaust air handling units.ACU controller DIN can be installed in a control cabinet in a simple, intuitive way, as it is compatible with the DIN-type mounting rail standard. Peripheral components are connected to the controller, which is the central unit, through detachable terminal strips. The enclosure has clear descriptions consisting of a letter symbol, numbering and a graphic element indicating the nature of the connector. With this solution, the user saves space and time.

Ask about this product
product description
downloads

Features:

  •  room temperature control
  •  cascade temperature control
  •  supply temperature limitation
  •  taking the outside temperature into account in the control
  •  control of water and/or electric heater
  •  water or direct evaporation cooler control
  •  control of the heat recovery system
  •  mixing chamber control
  •  thermal protection of fan motors
  •  antifreeze protection of the water heater
  •  recovery protection against frostbite
  •  electric heater protection
  •  control of dampers
  •  monitoring the condition of filters
  •  fan compression control
  •  cooperation with external devices
  •  calendar function:
    • weekly clock
    • three time zones in a day
    • blocking of selected functions in a given zone
    • Determination of expenditures for drives with an inverter individually for each zone
  •  service functions
  •  function of returning to factory values
  •  MODBUS RTU communication protocol - up to two networks
Digital inputs:
motor protection
2 inputs
differential pressure switches (filters and fans)
2 inputs
heater alarm
1 input
co-. with headquarters
1 input
remote control
1 input
Universal inputs:
  • for 0-10V signal from the temperature transmitter
  • and/or measuring the return water temperature from the heater
  • and/or measuring the temperature of the water return from the cooler
  • and/or digital input function for ON/OFF
  • and/or AUTO/MANUAL switching
  • and/or radiator alarm
  • and/or exchanger pressure switch
  • and/or filter pressure switch
1 input
Measurement inputs:
PT 1000 temperature sensors
4 inputs
Digital (relay) outputs:
fan control
2 outputs
control of the heating medium pump
1 output
control of throttle actuators
2 outputs
working signal for external systems
1 output
alarm signal for external systems
1 output
cooling demand signal
1 output
Analog outputs:
0-10V signal
3 (4*) outputs
Communication port:
RS 485 MODBUS protocol

*To the ACU controller. DIN 4 devices controlled by analog signal can be connected. This is possible because one of the analog outputs - Y2 - can operate 2 devices (heater and cooler). The required condition is that they are not switched on at the same time. The COOL output is used for this, where Y2 is switched between the two terminals of this output for the heating or cooling sequence, respectively.