SZS-D-ACU L

Universal control cabinet SZS-D-ACU L is an alternative to control units offered by manufacturers of air handling units. It is equipped with ACU L DIN controller, so it can work with most supply and supply/exhaust air handling units available on the market. Made on the basis of modular plastic housing. For each control cabinet is designed comprehensive technical documentation, prepared in accordance with the guidelines of the customer. We also supply automation components appropriately selected for the indicated air handling unit.

For an accurate quote, please contact: biuro@conel.pl

 

Dimensions 319x535x144mm (3x12 modules)
Housing Plastic
Degree of protection IP65
Implementation Internal

In addition to ready-made control cabinets, we also offer prefabrication of control cabinets in other designs.

 

Ask about this product
product description
downloads

Features:

  •  room temperature control
  •  cascade temperature control
  •  supply temperature limitation
  •  inclusion of external temperature in the control
  •  control of humidity in the room
  •  cascading humidity control
  •  control of the amount of CO2 in the room
  •  control of pressure differences in channels
  •  control of water and/or electric heater
  •  water or direct evaporation cooler control
  •  control of the heat recovery system
  •  mixing chamber control
  •  thermal protection of fan motors
  •  antifreeze protection of the water heater
  •  recovery protection against frostbite
  •  electric heater protection
  •  control of dampers
  •  monitoring the condition of filters
  •  fan compression control
  •  cooperation with external devices
  •  calendar function:
    • weekly and annual clock
    • four time zones in a day
    • blocking of selected functions in a given zone
    • Determination of expenditures for drives with an inverter individually for each zone
    • change of settings for SUMMER / WINTER
  •  service functions
  •  function of returning to factory values
  •  alarm history (last 10)
  •  MODBUS RTU communication protocol - up to two networks
Digital inputs:
motor protection
2 inputs
differential pressure switches (filters and fans)
2 inputs
heater alarm
1 input
co-. with fire panel.
1 input
remote control
1 input
Universal inputs:
  • for 0-10V signal from the temperature transmitter
  • and/or measuring the humidity in the room
  • and/or moisture measurement in the duct
  • and/or external humidity measurement
  • and/or a CO2
  • and/or channel pressure transducer2
  • and/or measuring the return water temperature from the heater
  • and/or measuring the temperature of the water return from the cooler
  • and/or digital input function for ON/OFF
  • and/or AUTO/MANUAL switching
  • and/or radiator alarm
  • and/or exchanger pressure switch
  • and/or filter pressure switch
2 inputs
Measurement inputs:
PT 1000 temperature sensors
4 inputs
Digital (relay) outputs:
fan control
2 outputs
control of the heating medium pump
1 output
control of throttle actuators
1 output
working signal for external systems
1 output
alarm signal for external systems
1 output
cooling demand signal
1 output
Analog outputs:
0-10V signal
4 (5*) outputs
Communication port:
RS 485 protocol MODBUS RTU

*To the ACU controller. L DIN can be connected 5 devices controlled by analog signal. This is possible because one of the analog outputs - Y2 - can operate 2 devices (heater and cooler). The required condition is that they are not switched on at the same time. The COOL output is used for this, where Y2 is switched between the two terminals of this output for the heating or cooling sequence, respectively.